How to Size Wire for Long Runs — 100, 200, and 300 Feet

Electrical wire copper conductors
By WiredAndBuilt April 14, 2026 9 min read

In This Guide

You just finished running conduit 200 feet across the property to a subpanel in the shop. You used 12 AWG wire because that's what you had in the truck. Six months later, your table saw stalls under load and your LED shop lights flicker when the heater kicks on. That's voltage drop — and it's entirely preventable if you size the wire correctly before you dig the trench.

Wire sizing for long runs is one of the most practical skills in electrical work. It applies whether you're wiring a garage subpanel, an EV charger, a well pump, or a 240V shop tool 300 feet from your main panel. The math is straightforward. This guide walks through it.

Why Voltage Drop Matters

Every foot of wire has resistance. As current flows through that resistance, voltage is lost along the way — and that lost voltage doesn't power your tools or devices. At the end of a long run, your equipment sees less than what the panel is supplying.

The NEC considers a 3% voltage drop on a feeder or branch circuit acceptable. Industry best practice (and what I'd call the smart threshold) is to keep it under 3% for the feeders and 5% total from the service entrance to the furthest outlet. Beyond 5%, you're asking for trouble: motors overheat, devices misbehave, and you waste energy as heat in the wire itself.

The formula for voltage drop is:

VD = (2 × K × I × L) / CM

Where:

What are circular mils? In the US, wire size is measured in mils — one mil equals 1/1000 of an inch. A circular mil (CM) is simply the area of a circle with a 1-mil diameter. It gives us a direct way to express wire cross-section without dealing with pi and radius squared. You don't need to memorize CM values — just reference a wire size chart when you're in the field. But knowing it exists helps the formula make sense.

You can also use an online voltage drop calculator and skip the long division — which is what most working electricians do in the field. But understanding the formula helps you sanity-check the numbers.

The Voltage Drop Formula (Simplified)

Here's a fast way to estimate wire size without pulling out a calculator every time:

For copper wire at 120V, single-phase:

Required CM = (2 × 12.9 × Amps × Length) / Acceptable VD

If you want to stay under 3% drop on a 120V circuit: use 0.03 × 120V = 3.6V as your acceptable drop. For 240V circuits: 0.03 × 240V = 7.2V.

Plug in your numbers. Then compare the resulting circular mils to a wire size chart. Common copper AWG sizes and their circular mils:

Sizing Wire for 100-Foot Runs

A 100-foot run is common for garage subpanels, air compressors, and long branch circuits. Here's how wire size scales with load at 120V (copper, 3% drop):

For 240V circuits at 100 feet, voltage drop is less punishing since the higher voltage means the same wattage draws less current. But if you're running a 30-amp 240V circuit (like an electric dryer or EV charger), 10 AWG is still tight — use 8 AWG.

Sizing Wire for 200-Foot Runs

At 200 feet, the numbers get serious. You need roughly double the wire area compared to a 100-foot run for the same current. Here's where most DIYers undersize wire:

At 200 feet, the difference between 10 AWG and 8 AWG on a 20A circuit isn't subtle — you're looking at roughly a 4.8% drop with 10 AWG versus 3% with 8 AWG. That 1.8% difference translates to real motors stalling and lights dimming.

Sizing Wire for 300-Foot Runs

300 feet is where you start making real wire size decisions. Most stock at the supply house won't cut it for higher-amp circuits without jumping to large-gauge wire that's expensive and hard to pull. Consider whether you can bump the voltage (go to 240V if possible) or use a subpanel closer to the load.

Real-World Circuit Examples

EV Charger — 50A, 150-foot Run

A Level 2 EV charger pulling 50A at 240V over 150 feet: use 4 AWG copper or 2 AWG aluminum at 3% drop. Copper 6 AWG is too small (it would give you about a 4.5% drop). Yes, aluminum is fine for feeders this size and is significantly cheaper per foot.

Well Pump — 20A, 250-foot Run

A 230V well pump at 20A, 250 feet from the panel: use 6 AWG copper at 3% (or 4 AWG for margin). A 250-foot run with 10 AWG would drop over 8% — your pump motor will run hot and寿命 will suffer.

Shop Subpanel — 100A feeder, 180-foot Run

A 100A feeder to a detached shop 180 feet away: use 1 AWG copper or 3/0 aluminum. This is where aluminum really makes sense cost-wise — 3/0 AL runs about half the price of 1 AWG copper for the same ampacity. Terminations must be rated for aluminum.

NEC 3% Rule — When It Applies

The NEC 3% rule (technically Informational Note 4 in NEC 210.19) is a recommendation, not a code minimum in most jurisdictions. However:

Some inspectors do enforce the 3% rule strictly, especially on commercial jobs. Others don't check it at all. The right call: size for 3% even if your local inspector wouldn't fail you for 5%. The wire cost difference on a 200-foot run is usually $50–$100. That's cheap insurance against callbacks and unhappy customers.

Five Mistakes That Burn Runs

1. Using length of wire instead of one-way length in the formula. Voltage drop is calculated on one-way distance. If you use round-trip distance, you'll oversize your wire and waste money.

2. Ignoring the temperature rating of the wire. Wire ampacity changes with temperature. 75°C-rated THHN in a conduit with other conductors needs a correction factor. Use 75°C ampacities for most standard builds.

3. Skipping the derate for continuous loads. If you're pulling 100% of a 30A circuit continuously (like an EV charger), size the wire for 125% of the load — so 37.5A. That means you need wire rated for 40A, not 30A.

4. Forgetting three-phase. If you're on three-phase power (commercial/industrial), the voltage drop formula changes to: VD = (1.732 × K × I × L) / CM. The 1.732 (√3) factor accounts for the phase relationship. Sizing for three-phase with a single-phase formula gives you wrong numbers.

5. Not planning for future capacity. If you're trenching for a 60A subpanel but only installing a 30A breaker today, run the wire for 60A anyway. The trench is the expensive part, not the wire. Future-you will thank present-you.

Wire sizing isn't complicated once you understand the relationship between current, distance, and conductor area. The math takes 30 seconds with a calculator. The pain of having to re-pull a run because you undersized it takes hours and costs 10x what a bigger wire would have.

Run the numbers before you dig.


Working on a long-run project? Check out our guide on wiring 240V outlets for more on circuit sizing and breaker selection.